viii SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.2.1 Disconnecting a FRU from a Domain 4–34.2.1.1 Disconnecting a CMU/IOU 4–34.
4-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009When the tests are complete the program will return to the original menu. Selectc
Chapter 4 FRU Removal Preparation 4-71. Configuring into a domainTo configure CMU or IOU into the domain, enter the following command fromthe terminal
4-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Note – The display may vary depending on the XCP version.For details of the showh
Chapter 4 FRU Removal Preparation 4-9XSCF> showhardconfSPARC Enterprise M9000; + Serial:PA30601004; Operator_Panel_Switch:Locked;+ Power_Supply_
4-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Output for the showhardconf command (Continued) + Core:4; Strand:2;
Chapter 4 FRU Removal Preparation 4-11Output for the showhardconf command (Continued)2. Verify the status LEDs on the PCI cassette.The POWER LED shoul
4-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.3 Hot ReplacementIn hot replacement the Solaris OS does not need to be configu
Chapter 4 FRU Removal Preparation 4-13The command is menu-driven. The example continues using a FAN unit.The replacefru command will automatically tes
4-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009When the tests are complete the program will return to the original menu. Select
Chapter 4 FRU Removal Preparation 4-154.3.2 Confirming the Hardware1. Use the showhardconf command to confirm the new component has beeninstalled:XSCF
Contents ix4.5.3.3 SPARC Enterprise M8000 Server Three-Phase PowerFeed 4–314.5.3.4 SPARC Enterprise M9000 Server Single-Phase PowerFeed 4–324.5.3.5 SP
4-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Output for the showhardconf command (Continued) + Memory_Size:32 GB;
Chapter 4 FRU Removal Preparation 4-17Output for the showhardconf command (Continued)Refer to the showhardconf man page for more information.2. Verify
4-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.4 Cold ReplacementIn cold replacement all business operations are stopped. Col
Chapter 4 FRU Removal Preparation 4-192. Back up the system files and data as necessary.3. Log into the XSCF Shell and type the poweroff commandThe fo
4-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.4.2.2 From the Maintenance TerminalFollow the power-on procedure below using t
Chapter 4 FRU Removal Preparation 4-21XSCF> showhardconfSPARC Enterprise M9000; + Serial:PA30601004; Operator_Panel_Switch:Locked; + Power_Su
4-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Output for the showhardconf command (Continued) + Core:2; Strand:2;
Chapter 4 FRU Removal Preparation 4-23Output for the showhardconf command (Continued) MEM#00B Status:Normal; + Code:7f7ffe0000000000
4-24 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Output for the showhardconf command (Continued)Refer to the showhardconf man pag
Chapter 4 FRU Removal Preparation 4-25Note – When you choose three-phase power feed option, the dual power feedoption is always included.4.5.1.1 AC In
x SPARC Enterprise M8000/M9000 Servers Service Manual • August 20096.2.2.2 Adding a SPARC64 VII CPU Module to a DomainConfigured With SPARC64 VI 6–106
4-26 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 4-2 Internal Connection of Power Supply (Three-Phase Power Feed)To use th
Chapter 4 FRU Removal Preparation 4-274.5.1.2 Power SystemThere are two types of power system: single power and dual power.FIGURE 4-3 shows the concep
4-28 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.5.2.1 Power-On1. Turn on all the main line switches of the expansion cabinet.I
Chapter 4 FRU Removal Preparation 4-294.5.3.1 SPARC Enterprise M8000 Server Single-Phase Power FeedFIGURE 4-4 Main Line Switch Locations (Rear of the
4-30 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.5.3.2 SPARC Enterprise M8000 Server Single-Phase and DualPower FeedFIGURE 4-5
Chapter 4 FRU Removal Preparation 4-314.5.3.3 SPARC Enterprise M8000 Server Three-Phase Power FeedFIGURE 4-6 Main Line Switch Locations (Power Cabinet
4-32 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.5.3.4 SPARC Enterprise M9000 Server Single-Phase Power FeedFIGURE 4-7 Main Lin
Chapter 4 FRU Removal Preparation 4-334.5.3.5 SPARC Enterprise M9000 Server Single-Phase and DualPower FeedFIGURE 4-8 Main Line Switch Locations (Fron
4-34 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.5.3.6 SPARC Enterprise M9000 Server Three-Phase Power FeedFIGURE 4-9 Main Line
Chapter 4 FRU Removal Preparation 4-354.6 Emergency Switch-OffIn emergency situations (such as smoke or flames are coming from the server), youneed to
Contents xi11. XSCF Unit Replacement 11–111.1 Overview of the XSCFU 11–111.2 Active Replacement and Hot Replacement 11–511.3 Cold Replacement 11–1112.
4-36 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 4-10 Example of the External I/O Expansion Units Mounted in the Rack Spac
Chapter 4 FRU Removal Preparation 4-37Note – The SPARC Enterprise M8000 server comes with 22 short hook-and-loopfasteners and 4 long hook-and-loop fas
4-38 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.7.1.2 When Three External I/O Expansion Units MountedThis section provides an
Chapter 4 FRU Removal Preparation 4-392. Run the remaining cables along the left route.FIGURE 4-11 Cable Routing When Three External I/O Expansion Uni
4-40 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20093. Bind the cables connected to each external I/O expansion unit with a shorthoo
Chapter 4 FRU Removal Preparation 4-41FIGURE 4-12 Magnified View of Part A (M8000, rear view)
4-42 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.7.1.3 For Server Using Three-phase Power FeedNote – The server using three-pha
Chapter 4 FRU Removal Preparation 4-4310. Divide the remaining cables into three routes (about 12 cables per route), bindthe cables on each route with
4-44 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200911. Fasten the cables running along the left route to the cable holder with a sh
Chapter 4 FRU Removal Preparation 4-45FIGURE 4-16 Completed Cable Routing with Three External I/O Expansion Units Mounted(M8000, rear view)
xii SPARC Enterprise M8000/M9000 Servers Service Manual • August 200917. Crossbar Unit Replacement 17–117.1 Overview of XBUs 17–117.2 Cold Replacement
4-46 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.7.1.4 When One External I/O Expansion Unit MountedThis section provides an exa
Chapter 4 FRU Removal Preparation 4-47FIGURE 4-17 Cable Routing When One External I/O Expansion Unit Mounted (M8000, rear view)VentilationslitsPart AP
4-48 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. Bind the cables from the external I/O expansion unit with a shorthook-and-loo
Chapter 4 FRU Removal Preparation 4-49FIGURE 4-19 Magnified View of Part B (M8000, rear view)
4-50 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 4-20 Completed Cable Routing with One External I/O Expansion Unit Mounted
PA RTII MaintenancePart II explains how to remove and replace FRUs.The chapters are organized according to the FRU mounting locations.Chapter 6 starts
5-1CHAPTER5Internal Components AccessThis chapter explains how to access each unit of the server, in the following sections: Section 5.1, “How to Ope
5-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. Push the projection down below the handle.The part below the handle projects o
Chapter 5 Internal Components Access 5-35.3 How to Remove a DoorIf it is absolutely necessary to remove a door during maintenance, refer toFIGURE 5-2
Contents xiii24. Addition and Deletion of a RDPF Option, Power Cabinet, and M9000Expansion Cabinet 24–124.1 Addition and Deletion of Rack-mountable Du
5-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20095. Keep the door in a safe place.To reinstall the door, reverse the above steps f
Chapter 5 Internal Components Access 5-5The procedure for removing the side panel is follows.1. Using a Phillips screwdriver, completely loosen the on
5-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
6-1CHAPTER6Replacement of CPU/MemoryBoard Unit (CMU), CPU, and DIMMThis chapter explains the procedures for replacing the CPU/Memory board unit(CMU) a
6-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009For the version matching of firmware, see the SPARC EnterpriseM3000/M4000/M5000/M
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-3FIGURE 6-2 CMU Mounting Locations (Rear of the M9000 Base Cabinet)CMU#7CMU#6CMU
6-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-3 CMU Mounting Locations (Rear of M9000 with the Expansion Cabinet)TABLE
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-56.2 CPU UpgradeThis section describes the procedure to mount the SPARC64 VII pr
6-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094. Collect an XSCF snapshot to archive system status prior to upgrade.This will b
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-713. Sets the following for the CMU. Set up XSB. Set up the domain Set up the
xiv SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.4 I/O Unit B–8B.5 Hard Disk Drive B–10B.6 PCI Cassette B–10B.7 IOU Onboard Devi
6-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20096.2.2 SPARC64 VII Processors Added to an ExistingDomainAdding SPARC64 VII Process
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-98. Update the XCP version.For the firmware updating procedures, see the SPARC E
6-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 If you are upgrading an existing SPARC64 VI CPU module in an existing domain t
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-118. Confirm that the target domain has been correctly started.9. Confirm no abn
6-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098. Confirm that the target domain has been correctly started.9. Confirm no abnor
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-13c. Execute the showboards command to check the use states of the devices andre
6-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20093. Prepare the CMU that is to be replaced. Active replacement:From the terminal
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-15Note – DDC_A is displayed only for the M8000.b. From the replacement parts lis
6-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-5 Removing the CMU (Front of the M8000)1123
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-17FIGURE 6-6 Removing the CMU (Rear of the M9000 Base Cabinet)7. Place the remov
Contents xvD. UPS Controller D–1D.1 Overview D–1D.2 Signal Cable D–1D.3 Configuration of Signal Lines D–2D.4 Power Supply Conditions D–4D.4.1 Input Ci
6-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200910. Replace parts.In CMU replacement:Remove all the CPUs and DIMMs mounted in th
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-19For DIMM replacement:Replace each swap target DIMM mounted in the removed CMU
6-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200913. Mount the replacement CMU by following the removal instructions in Step 6 in
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-2116. Confirm that the replacement components are normal by using theshowhardcon
6-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20095. Switch off all main line switches for the AC section (ACS) in the power suppl
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-239. Remove the cover of the CMU.a. Pull the two latches on the connector side o
6-24 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Note – Mount the dummy (filler) unit in the same manner as CMU. Since the samele
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-25Note – The showstatus command displays information on degraded components.20.
6-26 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-8 CPU Module and DIMM (MEM) Mounting LocationsCPUM#3CPUM#2CPUM#1CPUM#0M
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-276.5.1 Replacing a CPU ModuleTo replace the CPU module, use the CPU Module inse
xvi SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
6-28 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20091. Remove the CPU Module.a. Insert the tips on the extraction side of the CPU Mo
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-29FIGURE 6-11 CMU Guide Lock (Enlarged)Caution – When using the CPU Module inser
6-30 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-12 Lever Up the CPU ModuleCaution – When tilting the CPU Module inserti
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-31FIGURE 6-13 Remove the CPU Moduled. Remove the CPU Module insertion/extraction
6-32 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. Attach the replacement CPU Module.a. Slide and insert the guide pin on the DD
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-33FIGURE 6-15 CMU Guide Lock (Enlarged)
6-34 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009b. Fit the guide pin on the heat sink side of the CPU Module into the groove oft
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-35FIGURE 6-17 Set CPU Module Insertion/Extraction Tool
6-36 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-18 CMU Guide Lock (Enlarged)Caution – When using the CPU Module inserti
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-37FIGURE 6-19 Mounting the CPU ModuleCaution – Each CPU Module has two CMU guide
xviiPrefaceThis manual a maintenance manual for the SPARC Enterprise™ M8000/M9000servers. The manual explains basic operations and detailed replacemen
6-38 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009The CMU has 16 DIMMs as standard. The number of DIMMs that can be mountedon the
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-39FIGURE 6-20 shows an example of how to read the DIMM information displayed int
6-40 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 6-21 Memory Mounting ConditionsMEM#32AMEM#32BMEM#33AMEM#33BMEM#30AMEM#30B
Chapter 6 Replacement of CPU/Memory Board Unit (CMU), CPU, and DIMM 6-416.5.3 DIMM Replacement1. Open outward the tabs of the connector in which the D
6-42 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. Perform the above operation in reverse order to mount the DIMM.Note – To moun
7-1CHAPTER7I/O Unit (IOU) ReplacementThis chapter explains the replacement procedures for the I/O unit (IOU). It coversthe following: Section 7.1, “O
7-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – Adjust the positioning of the routes appropriately so that the cables d
Chapter 7 I/O Unit (IOU) Replacement 7-3FIGURE 7-1, FIGURE 7-2, FIGURE 7-3, FIGURE 7-4, and FIGURE 7-5 indicate the mountinglocations of IOUs.FIGURE 7
7-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 7-2 IOU mounting Locations (Front of the M9000 Base Cabinet)IOU#0IOU#2IOU#
Chapter 7 I/O Unit (IOU) Replacement 7-5FIGURE 7-3 IOU Mounting Locations (Rear of the M9000 Base Cabinet)IOU#7IOU#5IOU#3IOU#1
xviii SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Structure and Contents of This ManualThis manual is organized as described belo
7-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 7-4 IOU Mounting Locations (Front of M9000 with the Expansion Cabinet)IOU#
Chapter 7 I/O Unit (IOU) Replacement 7-7FIGURE 7-5 IOU Mounting Locations (Rear of M9000 with the Expansion Cabinet)TABLE 7-1 lists the abbreviated na
7-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20097.2 Active Replacement and HotReplacementThe active replacement procedure and hot
Chapter 7 I/O Unit (IOU) Replacement 7-9SPARC Enterprise M4000/M5000/M8000/M9000 Servers Dynamic Reconfiguration(DR) User’s Guide . For details on how
7-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009c. From here, perform the operation according to the guidance displayed in thema
Chapter 7 I/O Unit (IOU) Replacement 7-11FIGURE 7-7 Removing the IOU (Rear of M8000)1123
7-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 7-8 Removing the IOU (Front of M9000)1123
Chapter 7 I/O Unit (IOU) Replacement 7-13FIGURE 7-9 Removing the IOU (Rear of M9000)7. Place the removed IOU on an antistatic conductive mat.8. Dismou
7-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 7-10 Locations of PCI Slots and HDDs9. Mount the replacement IOU by follo
Chapter 7 I/O Unit (IOU) Replacement 7-15Note – In hot addition of an IOU, mount the CMU and IOU in the proper location.Otherwise, the added IOU may n
Preface xix Chapter 9 Power Supply Unit (PSU) Replacement:Explains the replacement procedures for a power supply unit (PSU). Chapter 10 Operator Pan
7-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200912. Confirm that the replacement components are normal by using theshowhardconf
Chapter 7 I/O Unit (IOU) Replacement 7-175. Switch off all main line switches for the AC section (ACS) in the power supplysystem.For details, see Sect
7-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20099. Dismount the HDD (or filler panel) and the PCI cards on the detached IOU,and
Chapter 7 I/O Unit (IOU) Replacement 7-19 From the console that is connected to XSCF, execute thepoweron -d <domain-id> command of XSCF for the
7-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
8-1CHAPTER8FAN Unit ReplacementThis chapter explains the replacement procedures for the FAN unit (FANU). Itcovers the following: Section 8.1, “Overvi
8-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098.1 Overview of the FAN UnitThis section provides an overview of FAN unit and des
Chapter 8 FAN Unit Replacement 8-3FIGURE 8-2 FAN Mounting Locations (Rear of the M8000)FAN_B#2-#7#7 #5#6 #4#3#2
8-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 8-3 FAN Mounting Locations (Front of the M9000 Base Cabinet)FAN_A#0-#3#1 #
Chapter 8 FAN Unit Replacement 8-5FIGURE 8-4 FAN Mounting Locations (Rear of the M9000 Base Cabinet)FAN_A#4-#15#15 #12#14 #11#9 #6#8 #5#13 #10 #7 #4
xx SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 Chapter 24 Addition and Deletion of a Rack-mountable Dual Power Feed Option,Powe
8-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 8-5 FAN Mounting Locations (Front of M9000 with the Expansion Cabinet)Expa
Chapter 8 FAN Unit Replacement 8-7FIGURE 8-6 FAN Mounting Locations (Rear of M9000 with the Expansion Cabinet)TABLE 8-1 lists the abbreviated names an
8-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098.2 Active Replacement and HotReplacementCaution – Each cabinet contains multiple
Chapter 8 FAN Unit Replacement 8-9c. From here, perform the operation according to the instructions displayed inthe maintenance menu.Check the states
8-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 8-9 Removing the FAN Unit (Rear of M8000)12
Chapter 8 FAN Unit Replacement 8-11FIGURE 8-10 Removing the FAN Unit (Front of M9000)21
8-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 8-11 Removing the FAN Unit (Rear of M9000)6. Place the removed FAN unit o
Chapter 8 FAN Unit Replacement 8-138. Go back to the terminal that is connected to XSCF, and perform the inputoperation according to the instructions
8-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 From a console that is connected to XSCF, log in to XSCF, and execute thepower
Chapter 8 FAN Unit Replacement 8-1512. Confirm that the XSCF STANDBY LED (green) on the operator panel remainslit. If it is blinking, wait until it re
Preface xxiSPARC Enterprise M8000/M9000Servers DocumentationThe manuals listed below are provided for reference.Book Titles Manual CodesSPARC Enterpri
8-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
9-1CHAPTER9Power Supply Unit (PSU)ReplacementThis chapter explains the replacement procedures for the power supply unit (PSU).It covers the following:
9-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009For details of the types and locations of power supply, see Section 4.5,“Power-On
Chapter 9 Power Supply Unit (PSU) Replacement 9-3FIGURE 9-2 PSU Mounting Locations (Rear of M8000 + Power Cabinet)Power cabinet
9-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 9-3 PSU Mounting Locations (Front of the M9000 Base Cabinet + Power Cabine
Chapter 9 Power Supply Unit (PSU) Replacement 9-5FIGURE 9-4 PSU Mounting Locations (Rear of the M9000 Base Cabinet + Power Cabinet)Power cabinet
9-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 9-5 PSU Mounting Locations (Front of M9000 with an Expansion Cabinet + Pow
Chapter 9 Power Supply Unit (PSU) Replacement 9-7FIGURE 9-6 PSU Mounting Locations (Rear of M9000 with an Expansion Cabinet + Power Cabinet)TABLE 9-1
9-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20099.2 Active Replacement and HotReplacementCaution – Each cabinet contains multiple
Chapter 9 Power Supply Unit (PSU) Replacement 9-9c. From here, perform the operation according to the instructions displayed inthe maintenance menu.Ch
xxii SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009External I/O Expansion Unit Product Notes C120-E456SPARC Enterprise M3000/M4000/
9-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 9-9 Removing the PSU (Front of the M9000 Base Cabinet)6. Place the remove
Chapter 9 Power Supply Unit (PSU) Replacement 9-11a. Perform operation according to instructions of messages. When the displayof the maintenance menu
9-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 From a console that is connected to XSCF, log in to XSCF, and execute thepower
Chapter 9 Power Supply Unit (PSU) Replacement 9-1312. Confirm that the XSCF STANDBY LED (green) on the operator panel remainslit. If it is blinking, w
9-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
10-1CHAPTER10Operator Panel ReplacementThis chapter explains the replacement procedures for the operator panel (OPNL). Itcovers the following: Sectio
10-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 10-1 OPNL Mounting Location (Front of the M8000)OPNL
Chapter 10 Operator Panel Replacement 10-3FIGURE 10-2 OPNL Mounting Location (Front of the M9000 Base Cabinet)OPNL
10-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 10-3 OPNL Mounting Location (Front of M9000 with the Expansion Cabinet)TA
Chapter 10 Operator Panel Replacement 10-5Note – When the maintenance work is completed, be sure to confirm the modeswitch setting and return the swit
Preface xxiii1. Manuals on the WebThe latest versions of all the SPARC Enterprise Series manuals are available at thefollowing websites.Global Sitehtt
10-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 10-4 Removing the OPNL10. Place the removed OPNL on an antistatic conduct
Chapter 10 Operator Panel Replacement 10-7 Press and hold down (for less than four seconds) the POWER switch on theoperator panel. From a console th
10-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
11-1CHAPTER11XSCF Unit ReplacementThis chapter explains the replacement procedures for an eXtended System ControlFacility unit (XSCFU). It covers the
11-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 11-1 XSCFU Mounting Locations (Front of the M8000)XSCFU_B#0XSCFU_B#1
Chapter 11 XSCF Unit Replacement 11-3FIGURE 11-2 XSCFU Mounting Locations (Front of the M9000 Base Cabinet)XSCFU_B#0XSCFU_B#1
11-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 11-3 XSCFU Mounting Locations (Front of M9000 with the Expansion Cabinet)
Chapter 11 XSCF Unit Replacement 11-511.2 Active Replacement and HotReplacementNote – To replace the XSCF Unit, you must consider the version of the X
11-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 11-4 Initial Page of the Maintenance MenuNote – DDC_A is displayed only f
Chapter 11 XSCF Unit Replacement 11-7FIGURE 11-5 Removing the XSCFU (Front of the M8000)121
xxiv SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Product HandlingMaintenanceCaution – Certain tasks in this manual should only be
11-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 11-6 Removing the XSCFU (Front of the M9000 Base Cabinet)7. Place the rem
Chapter 11 XSCF Unit Replacement 11-9Note – When your system is the SPARC Enterprise M9000 server with ExpansionCabinet, pay attention to the XSCF mes
11-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009For details of the unlockmaintenance command, see the SPARC EnterpriseM3000/M40
Chapter 11 XSCF Unit Replacement 11-11For the version matching of firmware, see the SPARC EnterpriseM3000/M4000/M5000/M8000/M9000 Servers XSCF User’s
11-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – If the dual power feed option is installed, switch off the main lines
Chapter 11 XSCF Unit Replacement 11-1311. Switch on all main line switches for the AC section (ACS) in the power supplysystem.12. Confirm that the XSC
11-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200917. Restore the original mode switch setting on the operator panel.Note – When
12-1CHAPTER12Hard Disk Drive (HDD)ReplacementThis chapter explains the replacement procedures for the hard disk drive (HDD). Itcovers the following:
12-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 12-1 HDD Mounting LocationsTABLE 12-1 lists the abbreviated name and numb
Chapter 12 Hard Disk Drive (HDD) Replacement 12-31. Unlock and open a door of the server.For details, see Chapter 5.2. Prepare for the replacement of
Preface xxvEmission of Laser Beam (Invisible)Caution – The main unit and high-speed optical interconnect cabinet containmodules that generate invisibl
12-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 12-2 Removing the HDD6. Place the removed HDD on an antistatic conductive
Chapter 12 Hard Disk Drive (HDD) Replacement 12-57. Mount the replacement HDD by following the removal instructions in Step 5 inreverse order. Align t
12-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 From a console that is connected to XSCF, log in to XSCF, and execute thepower
Chapter 12 Hard Disk Drive (HDD) Replacement 12-7Caution – Do not forcibly push the HDD when inserting it, even if it is not movingsmoothly. If the HD
12-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
13-1CHAPTER13PCI Slot Device ReplacementThis chapter explains the replacement procedures for devices that are mounted inthe PCI slots of an IOU. It co
13-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 Link cardIf PCI cards mounted in all the IOUs are not sufficient in number, th
Chapter 13 PCI Slot Device Replacement 13-3For the following devices, replacement procedures have the same steps except thatLEDs to be checked, eject
13-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. From the OS, execute the cfgadm -a command to verify the Ap_Id of the PCIcard
Chapter 13 PCI Slot Device Replacement 13-5Caution – When removing cables such as LAN cable, if your finger can't reach thelatch lock of the conn
xxvi SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Limitations and CautionsPower Control and Operator Panel Mode SwitchWhen you use
13-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009a. While grasping the lock bracket, turn it in the direction of the arrow andpus
Chapter 13 PCI Slot Device Replacement 13-7FIGURE 13-4 Loosening Screws of Latches
13-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 13-5 Removing the PCI Card
Chapter 13 PCI Slot Device Replacement 13-910. Mount the replacement PCI card on the PCI cassette. (Perform this work on theconductive mat.)FIGURE 13-
13-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Note – When the PCI cassette is removed from the IOU, the tab raises the front
Chapter 13 PCI Slot Device Replacement 13-11c. Align the PCI card with the center part of the lower latch of the cassette.Then, while pressing the PCI
13-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – If the card is short, move the screw at the bottom of the cassette as
Chapter 13 PCI Slot Device Replacement 13-13e. Using a Phillips screwdriver, tighten the green screw.Be sure to stop tightening the screw when the bot
13-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 If the lever of a PCI cassette cannot be inserted:a. When the lever of the PC
Chapter 13 PCI Slot Device Replacement 13-15b. If the lever stops halfway even when the PCI cassette is inserted again, pullthe PCI cassette out from
Preface xxviiFujitsu Welcomes Your CommentsIf you have any comments or requests regarding this document, or if you find anyunclear statements in the d
13-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200913.3 Hot ReplacementThe procedure for hot replacement is as follows.1. Unlock a
Chapter 13 PCI Slot Device Replacement 13-17b. Loosen the two screws at the rear of the PCI cassette, slide out the latch, andsecure it with screws. (
13-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – Align the PCI card with the slot guides, insert it carefully, and sec
Chapter 13 PCI Slot Device Replacement 13-1913.4 Cold ReplacementIn cold replacement, none of the replacement work is performed with themaintenance me
13-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – After stopping all the domains, be sure to switch off the main linesw
Chapter 13 PCI Slot Device Replacement 13-21a. Move the PCI card in the direction of the arrow, and mount it on the PCIcassette by inserting the part
13-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 Press and hold down (for less than four seconds) the POWER switch on theopera
14-1CHAPTER14CD-RW/DVD-RW Drive UnitReplacementThis chapter explains the replacement procedures for a CD-RW/DVD-RW drive unit(DVDU). It covers the fol
14-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 14-1 CD-RW/DVD-RW Drive Unit Mounting Location (Front of the M8000)DVDU
Chapter 14 CD-RW/DVD-RW Drive Unit Replacement 14-3FIGURE 14-2 CD-RW/DVD-RW Drive Unit Mounting Location (Front of the M9000 BaseCabinet)DVDU
SPARC Enterprise™M8000/M9000 ServersService ManualManual Code C120-E330-08ENPart No. 819-7877-15August 2009, Revision A
xxviii SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
14-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 14-3 CD-RW/DVD-RW Drive Unit Mounting Location (Front of M9000 with the E
Chapter 14 CD-RW/DVD-RW Drive Unit Replacement 14-51. Unlock and open a door of the server.For details, see Chapter 5.2. Stop all connection to the ta
14-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098. From the OS, execute the cfgadm -a command to verify that the status ofCD-RW/
Chapter 14 CD-RW/DVD-RW Drive Unit Replacement 14-7FIGURE 14-4 Removing the CD-RW/DVD-RW Drive Unit (Front of the M8000)12
14-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 14-5 Removing the CD-RW/DVD-RW Drive Unit (Front of the M9000)13. Place t
Chapter 14 CD-RW/DVD-RW Drive Unit Replacement 14-918. From the OS, execute the cfgadm -c configure TAPE_Ap_Id command toconfigure the tape drive unit
14-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20096. Connect the wrist strap clip to a cabinet grounding port, and attach the ban
Chapter 14 CD-RW/DVD-RW Drive Unit Replacement 14-1114.4 Cold ReplacementThe procedure is as follows.1. Unlock and open a door of the server.For detai
14-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20097. Remove the CD-RW/DVD-RW drive unit to be replaced. (See FIGURE 14-4 orFIGURE
15-1CHAPTER15Tape Drive Unit ReplacementThis chapter explains the replacement procedure for the tape drive unit (TAPEU). Itcovers the following: Sect
PA RTI Basic Information for Maintenance andTroubleshootingPart I provides maintenance information, explains methods of problem analysis,troubleshooti
15-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 15-1 Tape Drive Unit Mounting Locations (Front of the M8000)TAPEU
Chapter 15 Tape Drive Unit Replacement 15-3FIGURE 15-2 Tape Drive Unit Mounting Locations (Front of the M9000 Base Cabinet)TAPEU
15-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 15-3 Tape Drive Unit Mounting Locations (Front of M9000 with the Expansio
Chapter 15 Tape Drive Unit Replacement 15-515.2 Active ReplacementThe procedure is as follows.1. Unlock and open a door of the server.For details, see
15-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098. From the OS, execute the cfgadm -a command to verify that the status of taped
Chapter 15 Tape Drive Unit Replacement 15-7FIGURE 15-4 Removing the Tape Drive Unit (Front of the M8000)12
15-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 15-5 Removing the Tape Drive Unit (Front of the M9000)13. Place the remov
Chapter 15 Tape Drive Unit Replacement 15-919. From the OS, execute the cfgadm -a command to verify that the status of tapedrive unit and the CD-RW/DV
15-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20097. Connect the wrist strap clip to a cabinet grounding port, and attach the ban
Chapter 15 Tape Drive Unit Replacement 15-111. Unlock and open a door of the server.For details, see Chapter 5.2. Change the mode switch setting on th
15-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20099. Mount the replacement tape drive unit by following the removal instructionsi
16-1CHAPTER16Clock Control Unit ReplacementThis chapter explains the replacement procedure for the clock control unit (CLKU).It covers the following:
16-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 16-1 CLKU Mounting Locations (Front of the M9000 Base Cabinet)CLKU_B#0CLK
Chapter 16 Clock Control Unit Replacement 16-3FIGURE 16-2 CLKU Mounting Locations (Front of M9000 with the Expansion Cabinet)TABLE 16-1 lists the abbr
16-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009The procedure is as follows.1. Unlock and open a door of the server.For details,
Chapter 16 Clock Control Unit Replacement 16-5a. If the M9000 expansion cabinet is installed, slide the cable support bracketat the front of the clock
16-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20099. Mount the replacement CLKU by following the removal instructions in Step 7in
Chapter 16 Clock Control Unit Replacement 16-713. Confirm that the replacement components are normal by using theshowhardconf or showstatus command of
16-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
17-1CHAPTER17Crossbar Unit ReplacementThis chapter explains the replacement procedure for crossbar units (XBUs). It coversthe following: Section 17.1
1-1CHAPTER1Safety and ToolsThis chapter provides notes on handling the high-end server descriptions and rulesabout operation, and it lists the tools r
17-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 17-1 XBU Mounting Locations (Front of the M9000 Base Cabinet)XBU_B#0-#7#7
Chapter 17 Crossbar Unit Replacement 17-3FIGURE 17-2 XBU Mounting Locations (Front of M9000 with the Expansion Cabinet)TABLE 17-1 lists the abbreviate
17-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092. Change the mode switch setting on the operator panel from Locked to Service.N
Chapter 17 Crossbar Unit Replacement 17-5b. Using a Phillips screwdriver, turn the knob screws securing the left andright eject/lock levers 90 to 180
17-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20099. While grasping the eject/lock levers, properly align the crossbar unit with t
Chapter 17 Crossbar Unit Replacement 17-7Caution – If you are unable to obtain a torque screwdriver, finger tighten the clockcable connectors. Do not
17-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Note – The showstatus command displays information on degraded components.18. Re
18-1CHAPTER18AC Section ReplacementThis chapter explains the replacement procedures for AC sections (ACSs). It coversthe following: Section 18.1, “Ov
18-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009An ACS distributes AC input power from external sources to power supply units(PS
Chapter 18 AC Section Replacement 18-3FIGURE 18-2 ACS Mounting Location (Front of the M9000 Base Cabinet)ACS_B
1-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20091.1.2 Prompt NotationsThe following prompt notations are used in this manual.1.1.
18-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 18-3 ACS Mounting Locations (Front of M9000 with the Expansion Cabinet)TA
Chapter 18 AC Section Replacement 18-518.2 Cold ReplacementIn cold replacement, none of the replacement work is performed with themaintenance menu fro
18-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – After stopping all the domains, be sure to switch off the main lineswi
Chapter 18 AC Section Replacement 18-7c. Remove the power cables.Caution – When removing power cables, switch off the main line switches. Thepower cor
18-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 18-5 Removing the AC Section (Front of the M9000)121
Chapter 18 AC Section Replacement 18-9FIGURE 18-6 Removing the Three-phase AC Section (Power Cabinet)8. Place the removed AC section on an antistatic
18-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200912. Start (turn on power) all domains together. Take either of the following tw
19-1CHAPTER19DDC ReplacementThis chapter explains the replacement procedures for DDCs (DC-to-DC Converters).It covers the following: Section 19.1, “O
19-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 19-1 Mounting Locations of the DDCs (Front of the M8000)TABLE 19-1 lists
Chapter 19 DDC Replacement 19-319.2 Active Replacement and HotReplacementThe active replacement procedure and hot replacement procedure for the DDC ar
Chapter 1 Safety and Tools 1-31.1.3 Environmental Requirements for Using ThisProductThis product is a computer that is intended to be used in a comput
19-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009c. From here, perform operations according to the guidance displayed in themaint
Chapter 19 DDC Replacement 19-5FIGURE 19-3 Removing the DDC (Front of the M8000)5. Place the removed DDC on an antistatic conductive mat.121
19-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20096. Mount the replacement DDC by following the removal instructions in Step 4and
Chapter 19 DDC Replacement 19-72. Change the mode switch setting on the operator panel from Locked to Service.Caution – When the maintenance work is c
19-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20098. Place the removed DDC on an antistatic conductive mat.9. Mount the replacemen
Chapter 19 DDC Replacement 19-914. Restore the original mode switch setting on the operator panel.Note – When the maintenance work is completed, be su
19-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
20-1CHAPTER20Backplane ReplacementThis chapter explains the replacement procedure for backplanes (BPs). It covers thefollowing: Section 20.1, “Overvi
20-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009In cold replacement, none of the replacement work is performed with themaintenan
Chapter 20 Backplane Replacement 20-3FIGURE 20-2 BP Mounting Locations (Front of the M9000 Base Cabinet)BP_B
1-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20091.2 PrecautionsThe following notes must be observed in maintenance work:1.2.1 Ope
20-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-3 BP Mounting Locations (Front of M9000 with the Expansion Cabinet)TAB
Chapter 20 Backplane Replacement 20-52. Change the mode switch setting on the operator panel from Locked to Service.Note – When the maintenance work i
20-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20096. Connect the wrist strap clip to a cabinet grounding port, and attach the band
Chapter 20 Backplane Replacement 20-7 M9000 (See FIGURE 20-7):Perform the following operations from the rear of the unit:a. Pull all mounted CMUs off
20-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-4 Preparation for Accessing BP_A (Rear of the M8000)
Chapter 20 Backplane Replacement 20-9FIGURE 20-5 Preparation for Accessing BP_B (Front of M9000)8. Remove the BP to be replaced. M8000 (See FIGURE 20
20-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009c. Arrange the cables so that the connectors do not get caught in anythingwhile
Chapter 20 Backplane Replacement 20-11FIGURE 20-6 Removing the BP (Rear of the M8000)
20-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-7 Removing the BP (Front of the M9000)9. Place the removed BP on an a
Chapter 20 Backplane Replacement 20-1311. Switch on all main line switches for the AC section (ACS) in the power supplysystem.12. Confirm that the XSC
Chapter 1 Safety and Tools 1-51.2.3 Conversion and Reuse of This ProductIf this product is converted or a used article of this product is overhauled f
20-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200920.2.2 PSU BPFIGURE 20-8, FIGURE 20-9, and FIGURE 20-10 show the mounting locat
Chapter 20 Backplane Replacement 20-15FIGURE 20-9 PSUBP Mounting Locations (Front of the M9000 Base Cabinet)PSUBP_A#0PSUBP_A#1PSUBP_A#2
20-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-10 PSUBP Mounting Locations (Front of M9000 with the Expansion Cabine
Chapter 20 Backplane Replacement 20-172. Change the mode switch setting on the operator panel from Locked to Service.Note – When the maintenance work
20-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009c. Using a Phillips screwdriver, loosen the three thumb screws on the right sid
Chapter 20 Backplane Replacement 20-19FIGURE 20-11 Removing the PSUBP (Front of the M8000)PSUBP_BPSUBP_A
20-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-12 Removing the PSUBP (Front of the M9000)9. Place the removed BP on
Chapter 20 Backplane Replacement 20-2113. Start (turn on power) all domains together. Take either of the following twoactions: Press and hold down (f
20-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-13 FANBP Mounting Locations (M8000)FANBP_C#1FANBP_C#0Front Rear
Chapter 20 Backplane Replacement 20-23FIGURE 20-14 FANBP Mounting Locations (Rear of the M9000 Base Cabinet)FANBP_BFANBP_A
1-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – Be sure to wear an antistatic wrist strap when handling components.Plac
20-24 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-15 FANBP Mounting Locations (Rear of M9000 with the Expansion Cabinet
Chapter 20 Backplane Replacement 20-252. Change the mode switch setting on the operator panel from Locked to Service.Caution – When the maintenance wo
20-26 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009a. Remove all six FAN units. (See Chapter 8) After the FAN units are removed,re
Chapter 20 Backplane Replacement 20-27a. Using a Phillips screwdriver, loosen two thumb screws on each the left andright sides of the FANBP (FANBP_A o
20-28 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 20-17 Removing the FANBP (Front of M8000)
Chapter 20 Backplane Replacement 20-29FIGURE 20-18 Removing the FANBP (Rear of M9000)9. Place the removed BP on an antistatic conductive mat.10. Mount
20-30 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200913. Start (turn on power) all domains together. Take either of the following tw
21-1CHAPTER21Sensor Unit ReplacementThis chapter explains the replacement procedure for the sensor unit (SNSU). Itcovers the following: Section 21.1,
21-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 21-1 Mounting Location of the SNSU (Front of the M8000)SNSUSNSU
Chapter 21 Sensor Unit Replacement 21-3FIGURE 21-2 SNSU Mounting Location (Front of the M9000 Base Cabinet)SNSU
2-1CHAPTER2Product Overview andTroubleshootingThis chapter provides information that is required in troubleshooting.This information is explained in t
21-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 21-3 SNSU Mounting Location (Front of M9000 with the Expansion Cabinet)TA
Chapter 21 Sensor Unit Replacement 21-5The procedure is as follows.1. Unlock and open a door of the server.For details, see Chapter 5.2. Change the mo
21-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009b. While grasping the thumb screws, pull out the SNSU carefully from the slot.FI
Chapter 21 Sensor Unit Replacement 21-7FIGURE 21-5 Removing the SNSU (Front of the M9000)8. Place the removed SNSU on an antistatic conductive mat.9.
21-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200912. Start (turn on power) all domains together. Take either of the following two
22-1CHAPTER22Media Backplane ReplacementThis chapter explains the replacement procedure for media backplanes (MEDBPs). Itcovers the following: Sectio
22-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 22-1 MEDBP Mounting Location (Rear of the M8000)MEDBP
Chapter 22 Media Backplane Replacement 22-3FIGURE 22-2 MEDBP Mounting Location (Front of the M9000 Base Cabinet)MEDBP
22-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 22-3 MEDBP Mounting Locations (Front of M9000 with the Expansion Cabinet)
Chapter 22 Media Backplane Replacement 22-522.2 Cold ReplacementIn cold replacement, none of the replacement work is performed with themaintenance men
PleaseRecycleCopyright 2007-2009 FUJITSU LIMITED, 1-1, Kamikodanaka 4-chome, Nakahara-ku, Kawasaki-shi, Kanagawa-ken 211-8588, Japan. All rightsreserv
2-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009The front and rear views of FIGURE 2-1, FIGURE 2-2, FIGURE 2-4, FIGURE 2-5, FIGUR
22-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – After stopping all the domains, be sure to switch off the main lineswi
Chapter 22 Media Backplane Replacement 22-7FIGURE 22-4 Removing the MEDBP (Front of the M8000)
22-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 22-5 Removing the MEDBP (Front of the M9000)9. Place the removed MEDBP on
Chapter 22 Media Backplane Replacement 22-9 From a console that is connected to XSCF, execute the poweron -a commandof XSCF.The power to all the doma
22-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
23-1CHAPTER23Switch Backplane ReplacementThis chapter explains the replacement procedure for switch backplanes (SWBPs). Itcovers the following: Secti
23-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 23-1 SWBP Mounting Location (Rear of the M8000)SWBP
Chapter 23 Switch Backplane Replacement 23-3FIGURE 23-2 SWBP Mounting Location (Front of the M9000 Base Cabinet)SWBP
23-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 23-3 SWBP Mounting Locations (Front of M9000 with the Expansion Cabinet)T
Chapter 23 Switch Backplane Replacement 23-523.2 Cold ReplacementIn cold replacement, none of the replacement work is performed with themaintenance me
Chapter 2 Product Overview and Troubleshooting 2-32.1.1 SPARC Enterprise M8000 ServerFIGURE 2-1 Front View - M8000PSUDDCXSCFUTAPEUDVDUSNSUFAN_BCMUAir
23-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Caution – After stopping all the domains, be sure to switch off the main lineswi
Chapter 23 Switch Backplane Replacement 23-7FIGURE 23-4 Removing the SWBP (Rear of the M8000)
23-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 23-5 Removing the SWBP (Front of the M9000)9. Place the removed SWBP on a
Chapter 23 Switch Backplane Replacement 23-913. Start (turn on power) all domains together. Take either of the following twoactions: Press and hold d
23-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
24-1CHAPTER24Addition and Deletion of a RDPFOption, Power Cabinet, and M9000Expansion CabinetThis chapter explains the procedures for adding and delet
24-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200924.1 Addition and Deletion ofRack-mountable Dual Power FeedThis section explains
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-3FIGURE 24-1 RDPF Mounting Location (M8000)TABLE 24-1
24-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009The procedure is as follows.1. Unlock and open a door of the server.For details,
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-5c. Remove the connector panel (together with a thumb
2-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-2 Rear View - M8000FAN_BACSAir FilterIOU
24-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009g. Mount the dual power feed unit (with four screws) on the two poles at thefron
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-7FIGURE 24-4 Mounting the Cable (Rear of M8000)m. Mou
24-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 24-5 Mounting the Connector Unit (Rear of M8000)o. Mount the two brackets
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-9FIGURE 24-6 Mounting the Frame for ACS Mount (Rear o
24-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 24-7 Removing the ACS (Rear of M8000)s. Mount nine power supply units (P
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-11FIGURE 24-8 Mounting the PSU (Front of the M8000)9.
24-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 From a console that is connected to XSCF, execute the poweron -a commandof XS
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-13 Adding or deleting a power cabinet for the SPARC
24-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 24-10 M9000 Base Cabinet + Power CabinetPower cabinet
Chapter 24 Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet 24-15FIGURE 24-11 M9000 Expansion Cabinet + Power Cabine
Chapter 2 Product Overview and Troubleshooting 2-5FIGURE 2-3 Internal View - M8000PSUBP_BPSUBP_AFANBP_CMEDBPSWBPFANBP_CBP_A
24-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 24-12 M9000 Base Cabinet + M9000 Expansion CabinetM9000 expansion cabine
25-1CHAPTER25Addition and Deletion of CMU,DIMM, IOU, HDD, PCI Cards andTAPEUThis chapter explains the procedures for installing new FRUs and removing
25-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Some FRUs can be actively added or actively deleted: Active addition or removal
Chapter 25 Addition and Deletion of CMU, DIMM, IOU, HDD, PCI Cards and TAPEU 25-3FIGURE 25-1 Initial Page of the Maintenance MenuNote – DDC_A is displ
25-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094. Add the FRUs.Some steps for adding a FRU are the same as for replacing a FRU.
Chapter 25 Addition and Deletion of CMU, DIMM, IOU, HDD, PCI Cards and TAPEU 25-525.2.1 Active DeletionFirst, select a unit to be deleted as described
25-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20093. Switch off all main line switches for the AC section (ACS) in the power suppl
A-1APPENDIXASystem ConfigurationThis appendix describes the installation conditions and configuration of the SPARCEnterprise server.A.1 Installation C
A-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Be sure to use the same type of CPUM in each pair (CPUM#0 and CPUM#1, orCPUM#2 an
Appendix A System Configuration A-3TABLE A-1 System Configuration for SPARC Enterprise M8000 ServerUnit Number CommentsCabinet1CMU1to4CPU module2or4•
2-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.1.2 SPARC Enterprise M9000 Server (Base Cabinet)FIGURE 2-4 Front View - M9000 (
A-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009A.2.2 SPARC Enterprise M9000 Server (Base Cabinet)The SPARC Enterprise M9000 serv
Appendix A System Configuration A-5TABLE A-2 System Configuration for SPARC Enterprise M9000 ServerUnit Number CommentsBase cabinet1CMU1to8CPU module2
A-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009A.2.3 SPARC Enterprise M9000 Server (Base Cabinet +Expansion Cabinet)This configu
Appendix A System Configuration A-7A maximum of 16 CMUs (64 CPU chips / 128 cores) and 16 IOUs can be mounted inthis model. A total of 128 core expans
A-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Slot#0, 2, 4, 6: PCI-EX short cards or IOU onboarddevice cardsSlot#1, 3, 5, 7: PC
Appendix A System Configuration A-9Single-phase and dual power feed optionPower cabinet(three-phase power feed option: includes 2 units ofAC section)*
A-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
B-1APPENDIXBComponentsThis Appendix describes each component making up SPARC Enterprise.For the most up-to-date information, contact a certified servi
B-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009XSCF unit (M8000/M9000 Servers for basecabinet) B.11XSCFU_B Chapter 11XSCF Unit (
Appendix B Components B-3Note – *1 It uses the DR function. It is available in the configuration in which all theXSB on the target FRU can be detached
Chapter 2 Product Overview and Troubleshooting 2-7FIGURE 2-5 Rear View - M9000 (Base Cabinet)FAN_AAir FilterIOUCMU
B-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.1 CPU Memory Board UnitThe CPU memory board unit (CMU) consists of a CPU memory
Appendix B Components B-5 For the bus connecting SC and SC as well as SC and crossbar unit, a high-speedlink is used. For the bus connecting SC and
B-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 A dedicated LSI for CPU is mounted. One CPU chip is mounted on a CPU module. I
Appendix B Components B-7B.3 MemoryThe type of memory used is DIMM.FIGURE B-3 shows the memory.FIGURE B-3 MemoryThe memory has the following character
B-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.4 I/O UnitAn I/O Unit (IOU) consists of an I/O board (IOB) with two types of co
Appendix B Components B-9 An IOU can be added or removed using the DR function during systemoperation. Active maintenance of PCI slots is possible u
B-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.5 Hard Disk DriveThe hard disk drive (HDD) is mounted on an IOU. Up to four HD
Appendix B Components B-11FIGURE B-6 shows the PCICS.FIGURE B-6 PCI Express Short card cassette (PCICS)The PCI cassette has the following characterist
B-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.7 IOU Onboard Device CardThe IOU onboard device card (IOUA) is an option for m
Appendix B Components B-13B.8 Link Card (External I/O Expansion UnitConnection Card)The external I/O expansion unit connection card includes two link
2-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-6 Internal View - M9000 (Base Cabinet)PSUBP_AMEDBPSWBPFANBP_BBP_BFANBP_A
B-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.9 Crossbar UnitA crossbar unit (XBU: formal abbreviation is XBU_B) is mounted
Appendix B Components B-15 The XBU has a normal mode and a degraded mode. In normal mode, all eight setsoperate; and in degraded mode in which a fail
B-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.10 Clock Control UnitA clock control unit (CLKU: formal abbreviation is CLKU_B
Appendix B Components B-17B.11 XSCF UnitXSCF unit (XSCFU: eXtended System Control Facility unit) controls the system.Two types of XSCFU are available:
B-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE B-12 eXtended System Control Facility Unit (XSCFU_C)XSCFU has the followi
Appendix B Components B-19B.12 CD-RW/DVD-RW Drive UnitThe CD-RW/DVD-RW drive unit (DVDU) can be mounted on each cabinet. One forthe M8000/M9000 with t
B-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.13 Tape Drive UnitTape drive unit (TAPEU) is optional and can be mounted on ea
Appendix B Components B-21 The tape drive unit has a label bearing the printed component number andmanufacture's serial number.B.14 Operator Pan
B-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE B-16 Rear View of the Operator Panel (OPNL)OPNL has the following charact
Appendix B Components B-23B.15 Sensor UnitThe sensor unit (SNSU) monitors the intake-air temperature and humidity. In theM9000, this unit is mounted o
Chapter 2 Product Overview and Troubleshooting 2-92.1.3 SPARC Enterprise M9000 Server (ExpansionCabinet)FIGURE 2-7 Front View - M9000 (with the Expans
B-24 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.16 Power Supply UnitThe power supply unit (PSU) receives AC 200 to 240 V, and
Appendix B Components B-25B.17 AC SectionAC section (ACS) is positioned at the input side of the power supply unit (PSU), toprotect the system from el
B-26 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 The ACS_B is a single-phase power feed unit for the SPARC Enterprise M9000serv
Appendix B Components B-27FIGURE B-22 AC Section (ACSTPH_A) The ACSTPH_B is a unit that receives three-phase (star) power for the SPARCEnterprise M80
B-28 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE B-24 AC Section (ACSTPH_C) The ACSTPH_D is a unit that receives three-ph
Appendix B Components B-29 The ACS_D is an internal current power feed unit for the SPARC EnterpriseM8000 server/SPARC Enterprise M9000 server three-
B-30 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.18 FAN UnitThe FAN unit consists of two to three cabinet cooling FAN units. Tw
Appendix B Components B-31FIGURE B-28 FAN Unit (FAN_B)The FAN unit has the following characteristics. Active maintenance of a failed FAN unit during
B-32 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.19 Power CabinetA dual power feeder (DPF) and a three-phase AC power feeder ar
Appendix B Components B-33The power cabinet is shown in FIGURE B-29.FIGURE B-29 Power CabinetThe power cabinet has the following characteristics. Onl
2-10 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-8 Rear View - M9000 (with the Expansion Cabinet)FAN_AAir FilterIOUCMU
B-34 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.20 Rack-mountable Dual Power FeedRack-mountable Dual Power Feed (RDPF) is a de
Appendix B Components B-35B.21 BackplaneThe backplane (BP) is a printed circuit board (PCB) that has connectors and PCboard used to interconnect the c
B-36 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE B-32 Backplane (BP_B)The BP has the following characteristics. Only cold
Appendix B Components B-37B.22 DDCDC-DC converter (DDC_A) supplies DC power to electronic components mountedon the backplane (BP_A) for M8000. DDC_A r
B-38 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.23 PSU BackplanePSU backplane (PSUBP) is a PCB that has a connector for interc
Appendix B Components B-39B.24 FAN BackplaneThe FAN backplane (FANBP) is a PCB that has a connector for connecting multipleFAN units (FAN_A or FAN_B).
B-40 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE B-37 FAN Backplane (FANBP_B)FIGURE B-38 FAN Backplane (FANBP_C)FANBP has
Appendix B Components B-41 Because the FANBP is a built-in unit in the cabinet, only cold replacement isavailable for the FANBP. FANBP connects FAN
B-42 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009B.25 Media BackplaneThe Media backplane (MEDBP) is a PCB that has connectors for
Appendix B Components B-43B.26 Switch BackplaneSwitch backplane (SWBP) is a PCB that has connectors to connect Media BP tomultiple IOUs. The SWBP is a
Chapter 2 Product Overview and Troubleshooting 2-11FIGURE 2-9 Internal View - M9000 (with the Expansion Cabinet)2.2 Labels2.2.1 System Name Plate Labe
B-44 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 The SWBP has a label bearing the printed component number and manufacture&apos
C-1CHAPTERCExternal Interface SpecificationsThis appendix describes the specifications of the connectors provided on the SPARCEnterprise server unit:
C-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009C.2 UPC PortC.3 USB PortTABLE C-2 UPC PortSetting Pin No> Signal name Input/ou
Chapter C External Interface Specifications C-3C.4 Connection Diagram for Serial CableFIGURE C-1 Connection diagram for serial cable
C-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
D-1APPENDIXDUPS ControllerThis appendix explains the UPS controller (UPC) that controls the uninterruptiblepower supply (UPS) unit.D.1 OverviewThe UPS
D-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009D.3 Configuration of Signal LinesThis section provides the signal definitions.FIG
Appendix D UPS Controller D-3On: Indicates that the contact is closed.Off: Indicates that the contact is open.Note 1: Use a UPS that can normally supp
D-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009D.4 Power Supply ConditionsTABLE D-2 and TABLE D-3 show the power supply conditio
Appendix D UPS Controller D-5D.5 UPS CableThe UPS cable specifications are as follows: Connector shapeD-SUB9 pin male (receptacle side: female)DEU-9P
Copyright 2007-2009 FUJITSU LIMITED, 1-1, Kamikodanaka 4-chome, Nakahara-ku, Kawasaki-shi, Kanagawa-ken 211-8588, Japon. Tousdroits réservés.Entrée et
2-12 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 The ID label or EZ label is affixed on the front door of the server, and it in
D-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009D.6 ConnectionsThis section explains the connection between the UPC port and UPS.
Appendix D UPS Controller D-7D.7 UPC PortThis chapter describes the location of the UPC port and the UPS connections. UPC#0 connects with UPS#0. UPC#
D-8 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009
E-1APPENDIXEXSCF Unit Replacement When XCP1040 or 1041 Is in the ServerThe server must be updated to XCP 1050 or later.Note – XCP 1050 or later cannot
E-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200912. Wait until XSCF firmware reaches the ready state.This can be confirmed when t
Appendix E XSCF Unit Replacement When XCP 1040 or 1041 Is in the Server E-319. Confirm switching over between XSCFs works properly.a. When the READY L
E-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 200923. Turn the key switch on the operator panel from Service to Lock.
Abbreviations-1CHAPTERAbbreviationsAACS AC SectionACSTPH ACS Three-PhaseBBP BackplaneBUI Browser User InterfaceCCMB CPU Memory BoardCMU CPU/Memory Boa
Abbreviations-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009PPCICS PCI CassettePCI-ES PCI-Express ShortPFC Power Factor Correctio
Index-1IndexAAC section, B-25AC section replacement, 18-1ACScold replacement, 18-5active replacement, 4-2, 4-3CD-RW/DVD-RW, 14-4CMU, 6-12DDC, 19-3DVDU
Chapter 2 Product Overview and Troubleshooting 2-13FIGURE 2-10 M8000 Label Location Front RearStandard labelSystem Name Plate Label
Index-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009OPNL, 10-4PCI, 13-19PSU, 9-11PSU BP, 20-1servers BPs, 20-1SNSU, 21-4SWBP, 23
Index-3II/O box downlink card, B-13I/O unit, B-8I/O unit (IOU) replacement, 7-1ID label, 2-11incorporatingCMU/IOU, 4-6FRU into a domain, 4-6internal c
Index-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009hot replacement, 9-8PSU backplane, B-38PSU BPcold replacement, 20-1Rrack-mou
2-14 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-11 M9000 Label Location FrontRearStandard labelSystem Name Plate
Chapter 2 Product Overview and Troubleshooting 2-152.2.2 Labels About HandlingThe labels shown below, which are affixed on the high-end server, provid
2-16 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 Removing an I/O unit (IOU)2.3 Operator PanelThe operator panel controls the hi
Chapter 2 Product Overview and Troubleshooting 2-17FIGURE 2-12 Operator Panel Location (at the Front of M8000)2.3.2 Appearance and OperationsThe opera
2-18 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-13 Operator Panel2.3.3 LEDTABLE 2-1 lists the states of the server that
Chapter 2 Product Overview and Troubleshooting 2-19CHECK Amber Indicates the operating status of the SPARC Enterprise server.Off Normal state. Otherwi
2-20 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.3.4 SwitchThe operator panel has the mode switch, which sets the operation mod
Chapter 2 Product Overview and Troubleshooting 2-212.4 Determining Which DiagnosticsMethods To UseWhen an error occurs, a message is often displayed o
2-22 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 2-14 Diagnostic Method Flow ChartOS panic occurred or there’s anerror on
Chapter 2 Product Overview and Troubleshooting 2-232.5 Checking the Server and SystemConfigurationBefore and after maintenance work, the state and con
2-24 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Also some conditions can be checked based on the lit and/ or blinking state of t
Chapter 2 Product Overview and Troubleshooting 2-25 The software configuration and version can be checked in the Solaris OperatingSystem. Refer to th
2-26 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.5.2.2 Checking the Firmware ConfigurationLogin authority is required to check
Chapter 2 Product Overview and Troubleshooting 2-27You can find more detailed descriptions of Solaris OS Predictive Self-Healing at thewebsite below:h
2-28 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.6.2 Monitoring OutputTo understand error conditions, collect monitoring output
Chapter 2 Product Overview and Troubleshooting 2-292.6.3 Messaging OutputTo understand error conditions, collect messaging output information, by usin
2-30 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Each error message logged by the predictive self-healing architecture has a code
Chapter 2 Product Overview and Troubleshooting 2-31that has caused the error indicate that an error has occurred. The LEDs on theoperator panel (back)
vContentsPreface xvii1. Safety and Tools 1–11.1 Symbols 1–11.1.1 Text Conventions 1–11.1.2 Prompt Notations 1–21.1.2.1 Command syntax 1–21.1.3 Environ
2-32 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009CHECK(amber)Indicates either that the unit contains an error or that the unit is
Chapter 2 Product Overview and Troubleshooting 2-33XSCFU and IOU(display part forLAN)ACT Lit (green) Indicates that communication is being performedth
2-34 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.8 Using the Troubleshooting CommandsAfter the message in TABLE 2-8 is displaye
Chapter 2 Product Overview and Troubleshooting 2-35 console message log panic message log IPL message log2.8.2 Using the fmdump CommandThe fmdump c
2-36 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.8.3.2 fmadm faulty CommandThe fmadm faulty command can be used mainly to ident
Chapter 2 Product Overview and Troubleshooting 2-37Note – The error information remains in the Solaris OS even when replacement ofthe faulty component
2-38 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.9.1 iostat CommandThe iostat command iteratively reports terminal, drive, and
Chapter 2 Product Overview and Troubleshooting 2-39The following example shows output for one iostat command.2.9.2 prtdiag CommandThe prtdiag command
2-40 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009The following example shows output for the prtdiag command in verbose mode.# prt
Chapter 2 Product Overview and Troubleshooting 2-41========================= IO Cards =========================LSB Name Model--- -------------- ------
vi SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.1.3 SPARC Enterprise M9000 Server (Expansion Cabinet) 2–92.2 Labels 2–112.2.1 Sy
2-42 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009==================================== CPUs ====================================CP
Chapter 2 Product Overview and Troubleshooting 2-4300 PCI 0 2, 50, 1000 3, 1, 0 okay --, 133 scsi-pci1000,50 LSI,1064/pci@0,600000/pci@0/scsi@100 PCI
2-44 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.9.3 prtconf CommandSimilar to the show-devs command run at the ok prompt, the
Chapter 2 Product Overview and Troubleshooting 2-452.9.3.1 OptionsTABLE 2-15 describes options for the prtconf command and how those options canhelp t
2-46 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.9.4 netstat CommandThe netstat command displays the network status.2.9.4.1 Opt
Chapter 2 Product Overview and Troubleshooting 2-47The following example shows output for the netstat -p command.2.9.5 ping CommandThe ping command se
2-48 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.9.5.1 OptionsTABLE 2-17 describes options for the ping command and how those o
Chapter 2 Product Overview and Troubleshooting 2-492.9.6 ps CommandThe ps command lists the status of processes. Using options and rearranging thecomm
2-50 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20092.9.7 prstat CommandThe prstat utility iteratively examines all active processes
3-1CHAPTER3Periodic MaintenanceCaution – The information in this chapter and subsequent chapters is intended forservice engineers.Persons other than t
Contents vii2.8.3.1 fmadm config Command 2–352.8.3.2 fmadm faulty Command 2–362.8.3.3 fmadm repair Command 2–362.8.4 Using the fmstat Command 2–372.9
3-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009Each tape drive unit used for operation must be cleaned once every 24 hours ofope
Chapter 3 Periodic Maintenance 3-3Note – One concern about cleaning the air filters while power to the server is on isthat dislodged dust may be sucke
3-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 3-1 Removing Air Filters (Example for the M8000)3. Pull out all of the air
Chapter 3 Periodic Maintenance 3-5FIGURE 3-2 Removing of Air Filters (Example Using the M9000 Base Cabinet)3.3 Cleaning an Air Filter (I/O Unit)Each I
3-6 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009FIGURE 3-3 Removing of Air Filters (I/O Unit)3. Use a vacuum cleaner to remove du
4-1CHAPTER4FRU Removal PreparationThis chapter explains the required basic operations for replacing components, in thefollowing sections: Section 4.1
4-2 SPARC Enterprise M8000/M9000 Servers Service Manual • August 2009 Section 4.6, “Emergency Switch-Off” on page 4-354.1 Types of Replacement Proced
Chapter 4 FRU Removal Preparation 4-34.2 Active ReplacementIn active replacement the Solaris OS must be configured to allow the component tobe replace
4-4 SPARC Enterprise M8000/M9000 Servers Service Manual • August 20094.2.1.2 Disconnecting a PCI cardCaution – Before you remove the PCI cassette, mak
Chapter 4 FRU Removal Preparation 4-54.2.2 Disconnecting and Replacing a FRU1. From the XSCF Shell prompt, use the replacefru command:Note – DDC_A is
Comentarios a estos manuales